Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/04/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 03/31/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 36,000 BTUH SPLIT SYSTEM HT PUMP. OUTSIDE SECTION, MAX FUSE SIZE 35 AMPS. AIR HANDLER, ELEC DATA PLATE NOT MARKED. MAX FUSE SIZE, NO AUX HT STRIP IS 20 AMPS. - UNIT FUSED AT 30. COMPLETE MARKING DATA PLATE. LEAVE UNITS CORRECTLY FUSED. |