Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/13/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/08/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ YOU CANNOT CUT THE PLUG OFF FROM THE CORD ON CONDENSATE PUMP AND HARD WIRE INTO FURNACE. THIS ALTERS THE LISTING OF THE PUMP. REPLACE PLUG AND PLUG INTO A RECEPTACLE. THE WORK DONE DOES NOT MEET THE DESCRIPTION ON THE PERMIT. THERE IS A NEW A/C UNIT ADDED ALONG WITH A NEW ELEC. CIRCUIT, EVAP. COIL, REFER LINES. PLEASE RESUBMIT FOR PROPER DESCRIPTION OF WORK. |