Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/16/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) ALL CORRECTIONS HAVE BEEN MADE |
| 03/23/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ PLEASE SECURE SEAL TITE CONDUIT WITHIN 12" OF CONNECTION AND PROVIDE BLOCKS AND CLAMPS. RE-ROUTE ELEC. CORD FROM FURNACE AWAY FROM VENT CONNECTOR, COVER EXPOSED WOOD AND ELEC. WIRES WITHIN 6" OF VENT CONNECTOR. THE PLUG ON THE END OF THE CONDENSATE PUMP CANNOT BE CUTOFF AND HARD WIRED INTO FURNACE. DOING THIS ALTERS THE LISTING ON THE PUMP. PROVIDE A RECEPTACLE. CORRECT AND RECALL FOR INSPECTION. |
| 03/12/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0920*/ PLEASE HAVE YOUR CONTRACTOR CALL FOR AN INSPECTION WHEN SOMEONE WILL BE HOME. |