Permit: T04ME00116

Parcel: 136333270


Addresses:

8931 E DOLORES ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/19/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 1) YOU STILL NEED A HOSE CLAMP ON CONDENSATE PUMP
03/12/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) ROMEX CONNECTORS MUST BE USED WHERE POWER CORDS ENTER THE JUNCTION BOX INSIDE FURNACE, TIGHTEN ROMEX CONNECTOR ONTO WIRES. 2) PROVIDE A HOSE CLAMP WHERE PLASTIC HOSE CONNECTS TO CONDENSATE PUMP AND TO 3/8" COPPER. 3) REDUCER ON FURNACE VENT DOES NOT FIT CORRECTLY INTO TEE ON FLUE PIPE. 4) AN LB CANNOT BE CONNECTED TO A CIRCUIT PANEL WITH A CHASE NIPPLE. USE A NIPPLE WITH LOCKING NUTS OR OTHER APPROVED FITTING.