Permit: T04ME00115

Parcel: 114462610

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/16/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
03/16/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) REMOVE THE UNION FROM THE GAS LINE ON THE ROOF AND USE REVERSE THREAD COUPLING AND NIPPLE. 2) CONDENSATE DRAIN CANNOT CONNECT DIRECTLY TO A SEWER VENT. CALL ME TO DISCUSS ALTERNATE METHOD. JIM 909-4712.