Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 06/16/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/05/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN 2. RETURN AIR OPENING IN PLATFORM STILL NOT SIZED PER OPENING IN FURNACE 3. PROVIDE INSTALL INSTRUCTIONS FOR FURNACE IF YOU DON'T AGREE 4. PUMP CORD OK 5. BREAKER OK |
|
| 05/17/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) CUT THE OPENING IN THE FURNACE PLATFORM THE FULL SIZE OF THE RETURN AIR OPENING IN FURNACE. 2) DO NOT CUT THE PLUG OFF THE CORD FOR THE CONDENSATE PUMP. THIS ALTERS THE LISTING ON THE PUMP. 3) 50 AMP CIRCUIT BREAKER TOO LARGE. 40 AMP IS MAX. RECALL FOR INSP. |
|
| 05/13/2004 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :*/ CANCELLED. |