Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04ME00101
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
03/08/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) CONDENSORS 2 - 5 TON? WEST UNIT - RECONNECT EMT AT 3/4" EMT COUPLING. 2) CONTROL WIRING, NEEDS TO BE PROTECTED. 3) RET. AIR, BLOWER PLENIUM. EXPOSED NON PLENIUM RATED WIRE, PVC DRAIN MATERIEL INSIDE PLENIUM. 4) RELIEF AIR AT UPPER SIDE WALL, NO COMB AIR IN LOWER ROOM. |