Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/21/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) ALL CORRECTIONS HAVE BEEN MADE 2) FUSE STAT NOT NECESSARY FOR CONDENSATE PUMP |
| 03/10/2004 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/09/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) IDENTIFY CIRCUIT BREAKER. TIGHTEN ELEC. FITTINGS. GAS FLEX CONNECTOR CANNOT PENETRATE THE CABINET OF THE FURNACE. 2) HOOK UP OVERFLOW SENSOR ON CONDENSATE PUMP. 3) PROVIDE A TRAP ON CONDENSATEDRAIN. 4) PROVIDE MIN. 3 SCREWS IN VENT CONNECTOR. VENT CONNECTOR MUST HAVE MIN. ΒΌ" PER FOOT SLOPE. PROVIDE CLEARANCE FROM REFER LINEINSULATION. 5) INSULATE SUCTION LINE ALL THE WAY TO CONDENSOR. 6) PROVIDE A FUSE STAT FOR CONDENSATE PUMP - BE SURE TOFUSE CORRECTLY. 7) COIL DOES NOT FOT FURNACE, AIR LEAKING AT TOP AND BOTTOM OF COIL. 8) RETURN AIR OPENING IN PLATFORM NOT ADEQUATE. 9) SUPPORT REFER LINES AND ELEC. CONDUIT ON ROOF. T-STAT WIRE SHOULD BE IN CONDUIT OR INSTALLED WITH REFER LINE INSULATION. 10) CONDENSOR OVERFUSED. WIRE SIZE NOT ADEQUATE. MUST BE AT LEAST #8. DO NOT USE WHITE WIRE. SUPPORT FLEX CONDUIT 6' MAX. |
| 03/08/2004 |
MECHANICAL - FINAL |
|
Denied |
PLEASE HAVE YOUR CONTRACTOR CALL FOR AN INSPECTION WHEN SOMEONE WILL BE HOME |