Permit: T04ME00090

Parcel: 13604141A


Addresses:

2132 S CAMINO SECO

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/21/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ 1) ALL CORRECTIONS HAVE BEEN MADE 2) FUSE STAT NOT NECESSARY FOR CONDENSATE PUMP
03/10/2004 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*
03/09/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/1) IDENTIFY CIRCUIT BREAKER. TIGHTEN ELEC. FITTINGS. GAS FLEX CONNECTOR CANNOT PENETRATE THE CABINET OF THE FURNACE. 2) HOOK UP OVERFLOW SENSOR ON CONDENSATE PUMP. 3) PROVIDE A TRAP ON CONDENSATEDRAIN. 4) PROVIDE MIN. 3 SCREWS IN VENT CONNECTOR. VENT CONNECTOR MUST HAVE MIN. ΒΌ" PER FOOT SLOPE. PROVIDE CLEARANCE FROM REFER LINEINSULATION. 5) INSULATE SUCTION LINE ALL THE WAY TO CONDENSOR. 6) PROVIDE A FUSE STAT FOR CONDENSATE PUMP - BE SURE TOFUSE CORRECTLY. 7) COIL DOES NOT FOT FURNACE, AIR LEAKING AT TOP AND BOTTOM OF COIL. 8) RETURN AIR OPENING IN PLATFORM NOT ADEQUATE. 9) SUPPORT REFER LINES AND ELEC. CONDUIT ON ROOF. T-STAT WIRE SHOULD BE IN CONDUIT OR INSTALLED WITH REFER LINE INSULATION. 10) CONDENSOR OVERFUSED. WIRE SIZE NOT ADEQUATE. MUST BE AT LEAST #8. DO NOT USE WHITE WIRE. SUPPORT FLEX CONDUIT 6' MAX.
03/08/2004 MECHANICAL - FINAL Denied PLEASE HAVE YOUR CONTRACTOR CALL FOR AN INSPECTION WHEN SOMEONE WILL BE HOME