Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/03/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/02/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) COMPLETE ELECTRIC DATA PLATE. MAXIMUM FUSE SIZE, HEAT PUMP-25 AMP. UNIT FUSED AT 60 AMPS. AUXILARY HEAT STRIP, YES ? NO ? WHAT SIZE ? COMPLETE IT, LEAVE PROPERLY FUSED 2) CAN'T DUMP CONDENSATE INTO GUTTER WITHOUT DOWN SPOUT. MUST DRAIN OFF INTO AREA CAPABLE OF ABSORBING CON. NO SIDE WALKS, PAVED PARKING LOTS, ETC... |