Permit: T04ME00077

Parcel: 12809020C


Addresses:

4755 E 22ND ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/02/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) PAINT EXPOSED PVC WITH LATEX PAINT. BLOCK AND CLAMP PVC EVERY 4'. CONDENSATE CANNOT TERMINATE DIRECTLY INTO A SEWER VENT. 2) PROVIDE AN OUTSIDE AIR INTAKE WITH A FILTER. RECALL FOR INSPECTION.