Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ 1) ALL CORRECTIONS HAVE BEEN MADE | |
| 04/29/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SECURE THE ELEC DISCONNECT ON ROOF. WHITE WIRE CANNOT BE USED FOR HIGH VOLTAGE. PUT BLACK TAPE ON WHITE WIRES. NEED ACCESS TO CIRCUIT BREAKER PANEL. 2) HORIZONTAL SECTION OF CONDENSATE DRAIN DOES NOT HAVE ADEQUATE SLOPE. PROVIDE MIN. 1/8" PER FOOT SLOPE. RECALL FOR INSP. |
|
| 02/20/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ 25 PSI TEST ON NEW GAS PIPE IS OK. |