Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/12/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0935*/ YOU STILL HAVEN'T PAINTED THE EXPOSED PVC WITH LATEX PAINT AS REQUESTED ON LAST INSPECTION PLEASE PAY A RE-INSPECTION FEE PRIOR TO NEXT INSP. PLEASE SCHEDULE ANY ELEC. UPGRADE INSP. |
| 02/20/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 02/18/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. YOU CAN TERMINATE INTO THE RAIN GUTTER IF THE DOWNSPOUT GOES TO DIRT. IF USING PVC BLOCK AND CLAMP EVERY 4' AND PAINT WITH LATEX PAINT. |
| 02/11/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) JOINTS IN DUCT WORK NOT SEALED. 2) DUCT NEEDS TO BE BRACED AT FLEX CONNECTORS. 3) FLEX DUCT CONNECTORS - SUN SHIELD? 4) PROVIDE GROUND AT FLEX CONNECTORS. 5) CONDENSATE DRAIN?? NOT RUN, DO NOT DRAIN TO WET VENT. 48,000 BTHU COOL. 69 M. HEAT. COMPLETE/CORRECT/ RECALL FOR FINAL. |