Permit: T04ME00052

Parcel: 12713078B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04ME00052

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/12/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/CORRECTIONS HAVE BEEN MADE
03/18/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) CONDENSATE DRAINS CANNOT TERMINATE INTO A SEWER VENT. REMOVE ANY PIPE OR TEES THAT ARE OBSTRUCTING THE INSIDE OF THE VENT. VENTS ON TRAPS MUST BE DOWNSTREAM OF THE TRAP. TERMINATE DRAINS INTO AN APPROVED LOCATION. TRAP IS BACKWARDS ON MIDDLE UNIT 2) SECURE ELECTRIC SEAL TITE IF LONGER THAN 4' AND TIGHTEN CONNECTIONS TO EQUIPMENT. WIRE SIZE NOT ADEQUATE FOR 60 AMP CIRCUIT. MUST BE AT LEAST #6 WIRE. LABEL UNIT DATA PLATES WITH PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY 3) PROVIDE OUTSIDE AIR INTAKES 4) 2 X 4 SLEEPERS UNDER UNITS ARE NOT LONG ENOUGH AND MUST SPAN OVER THE ROOF JOISTS. JOISTS RUN EAST AND WEST 5) CORRECT AND RECALL FOR INSPECTION