Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. |
| 03/01/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 01/29/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ INSPECTED 3 TON GAS PACK. 1) 45 AMP FUSES ARE TOO LARGE. 40 AMP IS MAX. 2) CONDENSATE DRAIN CANNOT TERMINATE INTO A SEWER WASTE VENT. GO TO WITHIN 6" OF THE GROUND. PAINT ALL EXPOSED PVC WITH LATEX PAINT. RECALL FOR INSPECTION. |