Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04ME00024
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2008 | MECHANICAL - FINAL | Approved | COMPLIANCE WITH PREVIOUS CORRETION NOTES | |
| 12/04/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* UNIT #27 DISCONNECT OVERFUSED NEEDS 30 AMP MAKE CORRECTIONS AS NOTED FOR UNIT #17 UNIT #10 IS OK |
|
| 01/22/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ #017 I.D. WITH UNIT NO. 1) ROTATE ELECT SWITCH 90o. LEAVE FRONT TO OPEN WITH CLEARANCE. STABILIZE SWITCH. 2) RETURN AIR DUCT, SEAL AROUND SHEET METAL PATCH, SIDE OF DUCT. UNIT IS SUCKING AIR. 3) RUN CONDENSATE DRAIN TO ROOF LEADER HEAD WITH DOWN SPOUT, DOWN TO PLANTED AREA. NO ROOF TOP WET VENTS ACCEPTED FOR CONDENSATE RUN OFF. |