Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. |
| 01/26/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NEW VENT PIPE ON WATER HEATER PROVIDE MINIMUM 3 SCREWS IN EACH JOINT AND SCREW TO DRAFT DIVERTER AND 3 SCREWS IN EACH JOINT OF FURNACE VENT CONNECTOR. YOU MUST USE 3/8" COPPER TUBING FOR CONDENSATE PUMP NOT 1/4". PROVIDE FUSES IN ELECTRIC DISCONNECT FOR CONDENSOR. TIGHTEN SEAL TITE FITTING AT CONDENSOR. RECALL FOR INSPECTION |