Permit: T04ME00004

Parcel: 121121790


Addresses:

5369 E WILLARD ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/09/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 14 PSI TEST IS OK.
01/06/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) 3/8" I.D. GAS FLEX CONNECTOR NOT ADEQUATE FOR 125,000 BTU. VALVE MUST PROCEED GAS FLEX. 2) PROVIDE A PRESSURE TEST ON NEW GAS PIPING. 3) BLOCK AND CLAMP PVC ON ROOF EVERY 4'. PAINT EXPOSED PVC WITH LATEX PAINT. MUST TERMINATE WITHIN 6" OF GROUND. 4) SEAL ALL POP RIVETS AND INSULATION PIN HOLES ON EXPOSED DUCT ON ROOF AND ALSO SEAL S DRIVES BETTER. RECALL FOR INSPECTION.