Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04ME00002
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
04/06/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* | |
01/23/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) CAN'T TERMINATE CONDENSATE DRAINS OVER ROOF FACIA BOARDS. CONTINUE DOWN TO GROUND. 2) NORTH END UNIT [5 TON]. BLOCK 3/4" EMT FROM SERVICE TO UNIT. THIS UNIT IS NOT GROUNDED. NEED TO RECONNECT EMT LENGTHS, BLOCK AND CLAMP AS NECESSARY. 3) CENTER UNIT 3/4" PVC [UNDER UNIT] IS DISCONNECTED. |