Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2004 | INSP - FULL | Violation | 1). In kitchen, Class K extinguisher shall be mounted on wall and accessible. Currently extinguisher is on floor. TFC 906.7 | |
| 12/09/2004 | INSP - FULL | Violation | 2). Kitchen hood extinguishing system shall have required 6 month service as per TFC 904.11.6.4 which states; 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. |