Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T04FR00747

Parcel: 12412070A


Addresses:

1502 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T04FR00747

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2004 VIOL - MEANS OF EGRESS Approved
12/08/2004 VIOL - MEANS OF EGRESS Violation TFC 2003
1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of
not less than 90 minutes in case of primary power loss, the
sign illumination means shall be connected to an emergency
power system provided from storage batteries, unit equipment
or an on-site generator.

1. All exit sign shall have internal lighting and back-up emergnecy lighting.

TFC 2003
1003.6 Means of egress continuity. The path of egress travel
along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.

1. The parking block in front of the rear exit shall be place so vehicles will not block the full swing of the door.

TFC 2003
1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

1. keyed dead-bolt type of locks on rear exits must be replaced with thumb lach type of dead bolt or panic harware.

TFC 2003
1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists:
2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25mm)high on a contrasting background,