Case: T04FR00678

Parcel: 134210040


Addresses:

7040 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
02/01/2005 VIOL - FIRE PROTECTION SYSTEMS Approved Water motor gong was repaired, electrical bell was not wired. If they want to use the electric bell they will have to run a whole new electrical circuit and lock the breaker.
01/14/2005 VIOL - FIRE PROTECTION SYSTEMS Violation Feild notice given for sprinkler bell not working. Shall repair water motor gong or electric bell. TFD inspector will need to be on site when repairs are finshed to witness sprinkler bell operation. If using electric bell, must be on a dedicated electrical circuit and breaker lock out installed.
01/10/2005 VIOL - FIRE PROTECTION SYSTEMS Violation Received report WMG not working, new feild notice will be given.
01/07/2005 VIOL - FIRE PROTECTION SYSTEMS Violation Called and talked to manager, advised them I have not received any sprinkler report as of 01/07/2005. I have received a billing invoice that Macayo had it done , but no report.
11/23/2004 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6 Fire protection systems.
Fire sprinkler systems shall be inspected annually.
Field notice given.