Case: T04FR00465

Parcel: 12402043A


Addresses:

1605 E 1ST ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
12/01/2004 INSP - FULL Approved all approved
10/19/2004 INSP - FULL Violation 1). Kitchen. Added appliance is not covered under hood system. This added appliance shall be added to nozzle coverage, and never left unattended and shall be connected to system interconnection shutdown, 16 inch shield shall be added between open flame and deep frying operation, or appliance removed. TFC 904.11.2. TFC 904.11
10/19/2004 INSP - FULL Violation 2). Kitchen hood system is due for 6-month service TFC 904.11.6.4
10/19/2004 INSP - FULL Violation 3). Class K extinguisher shall be mounted on wall 30 feet within cooking operation. TFC 904.11.5
10/19/2004 INSP - FULL Violation 4). Fire alarm test and inspection report shall be submitted, and all repairs shall be completed. TFC 901.6
10/19/2004 INSP - FULL Violation 5). Fire sprinkler test and inspection report shall be submitted, and all repairs shall be completed. TFC 901.6
10/19/2004 INSP - FULL Violation 6). Door closure on "black room" shall be repaired. TFC 703.2.2
10/19/2004 INSP - FULL Violation 7). Windows in courtyard shall be repaired. TFC 110.1