Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/01/2004 |
INSP - FULL |
|
Approved |
all approved |
| 10/19/2004 |
INSP - FULL |
|
Violation |
1). Kitchen. Added appliance is not covered under hood system. This added appliance shall be added to nozzle coverage, and never left unattended and shall be connected to system interconnection shutdown, 16 inch shield shall be added between open flame and deep frying operation, or appliance removed. TFC 904.11.2. TFC 904.11 |
| 10/19/2004 |
INSP - FULL |
|
Violation |
2). Kitchen hood system is due for 6-month service TFC 904.11.6.4 |
| 10/19/2004 |
INSP - FULL |
|
Violation |
3). Class K extinguisher shall be mounted on wall 30 feet within cooking operation. TFC 904.11.5 |
| 10/19/2004 |
INSP - FULL |
|
Violation |
4). Fire alarm test and inspection report shall be submitted, and all repairs shall be completed. TFC 901.6 |
| 10/19/2004 |
INSP - FULL |
|
Violation |
5). Fire sprinkler test and inspection report shall be submitted, and all repairs shall be completed. TFC 901.6 |
| 10/19/2004 |
INSP - FULL |
|
Violation |
6). Door closure on "black room" shall be repaired. TFC 703.2.2 |
| 10/19/2004 |
INSP - FULL |
|
Violation |
7). Windows in courtyard shall be repaired. TFC 110.1 |