Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2004 | INSP - FULL | Violation | all approved | |
| 09/30/2004 | INSP - FULL | Violation | 1). Fire alarm test and inspection report shall be submitted, and repairs completed. TFC 901.6 | |
| 09/30/2004 | INSP - FULL | Violation | 2). Fire sprinkler test and inspection report shall be submitted, and repairs completed. TFC 901.6 | |
| 09/30/2004 | INSP - FULL | Violation | 3). Unable to test egress illumination lights during inspection. These shall be tested and documented. Report shall be submitted to TFD. TFC 901.6 | |
| 09/30/2004 | INSP - FULL | Violation | 4). Move all combustible boxes from elevator room. TFC 315.2.3 | |
| 09/30/2004 | INSP - FULL | Violation | 5). 6-month service shall be completed on hood extinguishing system in kitchen. TFC 904.11.6.4 | |
| 09/30/2004 | INSP - FULL | Violation | 6). All doors having automatic door closures shall ALWAYS kept closed. And door closures shall be maintained. This is violation of TFC 703.2.2 which states; 703.2.2 Hold-open devices and closers. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position. DO NOT BLOCK DOORS OPEN |
|
| 09/30/2004 | INSP - FULL | Violation | 7). Class K extinguisher in kitchen shall have annual service. |