Case: T04FR00418

Parcel: 12402034D


Addresses:

1701 E 1ST ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
12/01/2004 INSP - FULL Approved all aproved
11/08/2004 INSP - FULL Violation precitation letter sent
09/29/2004 INSP - FULL Violation ). All smoke detectors shall be tested and repaired, and log submitted to TFD. TFC 901.6
09/29/2004 INSP - FULL Violation 2). Fire alarm shall be tested and test report shall be submitted to TFD, and all repairs shall be completed. TFC 901.6
09/29/2004 INSP - FULL Violation 3). Egress Illumination lights are out of service in the following areas and shall be repaired or replaced;
09/29/2004 INSP - FULL Violation Basement, east stairway, 1st floor, and 2nd floor. TFC 901.6
4). All hallway-ceiling lights shall be covered, or electrically repaired. TFC 605.1
09/29/2004 INSP - FULL Violation 5). Kitchen: mount Class K portable fire extinguisher. TFC 901.6
09/29/2004 INSP - FULL Violation 6). Kitchen: 6-month service required for hood extinguishing system TFC 904.11.6.4