Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/20/2004 |
INSP - FULL |
|
Approved |
|
| 09/20/2004 |
INSP - FULL |
|
Violation |
1). Fire alarm test and inspection report shall be submitted. All repairs shall be made. Approved form is enclosed. TFC 901.6 |
| 09/20/2004 |
INSP - FULL |
|
Violation |
2). Fire sprinkler system test and inspection report shall be submitted. All repairs shall be made. Approved form is enclosed. TFC 901.6 |
| 09/20/2004 |
INSP - FULL |
|
Violation |
3). Fusible link on laundry chute shall be repaired. TFC 901.6 |
| 09/20/2004 |
INSP - FULL |
|
Violation |
4). Move ceiling light from within 18 inches of sprinkler head. TFC 315.2.1 |
| 09/20/2004 |
INSP - FULL |
|
Violation |
5). Required ceiling tiles are missing from Break room and computer room. TFC 703.1 |
| 09/20/2004 |
INSP - FULL |
|
Violation |
6). All combustible material shall be removed from 1st floor air handler room, and rated door shall remain closed. TFC 703.1 and TFC 315.2.3 |
| 09/20/2004 |
INSP - FULL |
|
Violation |
7). Close all doors with door closure attached. These are fire rated doors. TFC 703.2.2 |
| 09/20/2004 |
INSP - FULL |
|
Violation |
8). Extension cord shall be removed from Expo kitchen TFC 605.5 |
| 09/20/2004 |
INSP - FULL |
|
Violation |
9). 2nd floor video room. Hole in ceiling shall be repaired. TFC 703.1 |
| 09/20/2004 |
INSP - FULL |
|
Violation |
10). Boxes in elevator room shall be removed TFC 315.2.3 |
| 09/20/2004 |
INSP - FULL |
|
Violation |
11). All hood and vents shall be cleaned, all the way to exterior roof. And invoice-showing work done shall be furnished to TFD. |