Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T04FR00384
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2004 | INSP - FULL | Approved | ||
| 09/20/2004 | INSP - FULL | Violation | 1). Fire alarm test and inspection report shall be submitted. All repairs shall be made. Approved form is enclosed. TFC 901.6 | |
| 09/20/2004 | INSP - FULL | Violation | 2). Fire sprinkler system test and inspection report shall be submitted. All repairs shall be made. Approved form is enclosed. TFC 901.6 | |
| 09/20/2004 | INSP - FULL | Violation | 3). Fusible link on laundry chute shall be repaired. TFC 901.6 | |
| 09/20/2004 | INSP - FULL | Violation | 4). Move ceiling light from within 18 inches of sprinkler head. TFC 315.2.1 | |
| 09/20/2004 | INSP - FULL | Violation | 5). Required ceiling tiles are missing from Break room and computer room. TFC 703.1 | |
| 09/20/2004 | INSP - FULL | Violation | 6). All combustible material shall be removed from 1st floor air handler room, and rated door shall remain closed. TFC 703.1 and TFC 315.2.3 | |
| 09/20/2004 | INSP - FULL | Violation | 7). Close all doors with door closure attached. These are fire rated doors. TFC 703.2.2 | |
| 09/20/2004 | INSP - FULL | Violation | 8). Extension cord shall be removed from Expo kitchen TFC 605.5 | |
| 09/20/2004 | INSP - FULL | Violation | 9). 2nd floor video room. Hole in ceiling shall be repaired. TFC 703.1 | |
| 09/20/2004 | INSP - FULL | Violation | 10). Boxes in elevator room shall be removed TFC 315.2.3 | |
| 09/20/2004 | INSP - FULL | Violation | 11). All hood and vents shall be cleaned, all the way to exterior roof. And invoice-showing work done shall be furnished to TFD. |