Case: T04FR00384

Parcel: 134270010


Addresses:

7600 E BROADWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
10/20/2004 INSP - FULL Approved
09/20/2004 INSP - FULL Violation 1). Fire alarm test and inspection report shall be submitted. All repairs shall be made. Approved form is enclosed. TFC 901.6
09/20/2004 INSP - FULL Violation 2). Fire sprinkler system test and inspection report shall be submitted. All repairs shall be made. Approved form is enclosed. TFC 901.6
09/20/2004 INSP - FULL Violation 3). Fusible link on laundry chute shall be repaired. TFC 901.6
09/20/2004 INSP - FULL Violation 4). Move ceiling light from within 18 inches of sprinkler head. TFC 315.2.1
09/20/2004 INSP - FULL Violation 5). Required ceiling tiles are missing from Break room and computer room. TFC 703.1
09/20/2004 INSP - FULL Violation 6). All combustible material shall be removed from 1st floor air handler room, and rated door shall remain closed. TFC 703.1 and TFC 315.2.3
09/20/2004 INSP - FULL Violation 7). Close all doors with door closure attached. These are fire rated doors. TFC 703.2.2
09/20/2004 INSP - FULL Violation 8). Extension cord shall be removed from Expo kitchen TFC 605.5
09/20/2004 INSP - FULL Violation 9). 2nd floor video room. Hole in ceiling shall be repaired. TFC 703.1
09/20/2004 INSP - FULL Violation 10). Boxes in elevator room shall be removed TFC 315.2.3
09/20/2004 INSP - FULL Violation 11). All hood and vents shall be cleaned, all the way to exterior roof. And invoice-showing work done shall be furnished to TFD.