Inspection History Details
Inspection Status: Approved
Inspection History: INSP - REINSPECTION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2004 | INSP - REINSPECTION | Approved | all approved | |
| 10/01/2004 | INSP - REINSPECTION | Violation | 1). Egress illumination lights are out of service in basement TFC 1026 2). In addition, an inspection of each room found that many sprinkler heads are blocked by personal items such as boxes, clothing, shoes etc. This was found in the following room, but NOT limited to: 20,2,4,3, The Tucson Fire Code states: 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. Although sometimes, 18 inches below sprinkler heads may be impractical due to shelving space, etc…, enough room must be crated to obtain necessary water flow to all areas of closet. 3). In phone room there is a large amount of combustible material, that is excessive and blocking fire panel. All excessive combustible material shall be removed.. TFC 304.1 |