Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T04FR00354
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2004 | INSP - FULL | Approved | all aproved test report receieved | |
| 11/02/2004 | INSP - FULL | Approved | ||
| 10/07/2004 | INSP - FULL | Approved | ||
| 09/02/2004 | INSP - FULL | Violation | 1). Fire alarm shall be tested and test report submitted to TFD. All repairs shall be completed. TFC 906.1 | |
| 09/02/2004 | INSP - FULL | Violation | 2). Outside electrical J-Box to cooler shall have cover replaced. TFC 605.1 | |
| 09/02/2004 | INSP - FULL | Violation | 3). Remove combustible material from under stairs in lobby. TFC 315.2.2 | |
| 09/02/2004 | INSP - FULL | Violation | 4). Egress illumination lights shall be repaired in the following areas: laundry room and lobby. TFC 1010.5 | |
| 09/02/2004 | INSP - FULL | Violation | 5). Currently construction is being conducted. Requires separation walls in kitchen, hood extinguishing system and sewer and plumbing in kitchen. These shall be reviewed by City of Tucson Development Services Division for plans review and permits requirements. TFC 106 |