Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T04FR00323
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2004 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 609.7 Makeup air - Makeup air shall be supplied when operating kitchen hood system. | |
| 08/24/2004 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | Extension cords - Extension cords shall not be used as permanent wiring. Cords shall not be extended through cieling. | |
| 08/24/2004 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 605.4 Multiplug adapter - Multiplug adapters shall not be used. | |
| 08/24/2004 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 605.6 Unapproved conditions - Open wiring splices in freezer shall be repaired. | |
| 08/24/2004 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | Abatement of electrical hazards - Electrical wiring that is damaged shall not be used. Wiring to hood system blower motor on roof shall be repaired. |