Inspection History Details
Inspection Status: Compliance
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T04FR00320
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2004 | VIOL - MEANS OF EGRESS | Compliance | ||
07/29/2004 | VIOL - MEANS OF EGRESS | Correction Required | 1010.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. 1.) thourghout complex shall repair exit signs |
|
07/29/2004 | VIOL - MEANS OF EGRESS | Correction Required | 1003.3.1.8.1 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. 1.) Shall remove flush bolts from lobby doors. |
|
07/29/2004 | VIOL - MEANS OF EGRESS | Correction Required | 1010.4 Power source. Where emergency illumination is required in Section 1010.5, exit signs shall be visible under emergency illumination conditions. 1.) Shall repair or replace back up lighting in lobby. 2.) Shall repair or replace exit signs with battery back up power, some of the signs fail to work when tested. |