Case: T04FR00320

Parcel: 10704007B


Addresses:

1550 W GRANT RD


Inspection Status: Compliance

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T04FR00320

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Compliance

Date Description Inspector Results Comments
08/24/2004 VIOL - MEANS OF EGRESS Compliance
07/29/2004 VIOL - MEANS OF EGRESS Correction Required 1010.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated.

1.) thourghout complex shall repair exit signs
07/29/2004 VIOL - MEANS OF EGRESS Correction Required 1003.3.1.8.1 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.

1.) Shall remove flush bolts from lobby doors.
07/29/2004 VIOL - MEANS OF EGRESS Correction Required 1010.4 Power source. Where emergency illumination is required in Section 1010.5, exit signs shall be visible under emergency illumination conditions.

1.) Shall repair or replace back up lighting in lobby.
2.) Shall repair or replace exit signs with battery back up power, some of the signs fail to work when tested.