Case: T04FR00320

Parcel: 10704007B


Addresses:

1550 W GRANT RD


Inspection Status: Compliance

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T04FR00320

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Compliance

Date Description Inspector Results Comments
08/24/2004 VIOL - FIRE PROTECTION SYSTEMS Compliance
07/29/2004 VIOL - FIRE PROTECTION SYSTEMS Correction Required 906.2 General requirements. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.

1.) Shall replace missing fire extingushers in cabenits.
07/29/2004 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

1.) Shall repair or replace smoke detector in room 235. Need to have maids test smoke detectors in rooms when cleaning each and everytime.