Case: T04FR00312

Parcel: 11711096D


Addresses:

100 N STONE AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T04FR00312

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
10/11/2004 INSP - FULL Approved
08/18/2004 INSP - FULL Violation . TFC 906.1 All sprinkler shut off valves shall be labeled. TFC 906.11). Fire sprinkler test and inspection report shall be submitted. All repairs shall be completed
08/18/2004 INSP - FULL Violation 2). Fire alarm test and inspection report shall be submitted. All repairs shall be completed. TFC 906.1
08/18/2004 INSP - FULL Violation 3). Fire pump test and inspection report shall be submitted. All repairs shall be completed. TFC 906.1
08/18/2004 INSP - FULL Violation 4). Fire drill required. Date to be determined by September 22, 2004. TFC 404.2
08/18/2004 INSP - FULL Violation 6). Exit signs are out through basement n area. This includes, Maintenance Shop (cover arrow), 5 total. Repair all exit signs. TFC1010.3
08/18/2004 INSP - FULL Violation 7). Cover electrical faceplates, where wiring is exposed. Maintenance shop and record storage are among areas. TFC 605.1
8). Submit emergency generator test log sheet to TFD. TFC 604.3.2
100 North stone cont.
08/18/2004 INSP - FULL Violation 9). Holes shall be repaired, but not limited to the following areas; ceiling by rated hallway door, maintenance shop ceiling, fire control center. TFC 703.1
10). 36-inch aisle shall be created by maintenance shop. TFC 1004.3.1.1
08/18/2004 INSP - FULL Violation 8). Submit emergency generator test log sheet to TFD. TFC 604.3.2
08/18/2004 INSP - FULL Violation Pima County Print Shop.
11). Exit blocked by paper pallet. Shall be removed. TFC 1011.2
08/18/2004 INSP - FULL Violation IKE's coffee shop
12) Euscusion shall be refitted on sprinkler head in storage area.
TFC 906.1
13). Electrical panel in IKE's storage shall be remained closed at all times. TFC 605.1
08/18/2004 INSP - FULL Violation First floor empty office
14). Ceiling tile shall be replaced. 703.1
08/18/2004 INSP - FULL Violation Leopard lounge
15). Exit light shall be repaired 1010.3
08/18/2004 INSP - FULL Violation Small (intermediate roof)
16). Exit arrows are faded after several of Az heat years. These shall be repainted as per shown. TFC 1010.3.
17). Exit signs shall be illuminated for evening exits. 1010.3
18). Smoke detectors on air ducts shall be addressed on test results 906.1
08/18/2004 INSP - FULL Violation Suite 500B
19). Extension cord shall be removed through ceiling tiles. TFC605.5
08/18/2004 INSP - FULL Violation Suite 707
20). Extension cord shall be removed. TFC 605.5
08/18/2004 INSP - FULL Violation 21). 8th floor sprinkler room
Hole in sprinkler room shall be repaired TFC 703.1
08/18/2004 INSP - FULL Violation Suite 1105
22). Storage shall not be 2 feet with in ceiling TFC 315.2.1
08/18/2004 INSP - FULL Violation Roof;
23). Standpipes seem to painted shut, shall be loosened TFC 906.1
24). Hole around sprinkler head (computer room) shall be filled. TFC 906.1
Freight elevator room.
25). Hole in walls shall be repaired. 906.1
08/18/2004 INSP - FULL Violation