Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/11/2004 | INSP - FULL | Approved | ||
08/18/2004 | INSP - FULL | Violation | . TFC 906.1 All sprinkler shut off valves shall be labeled. TFC 906.11). Fire sprinkler test and inspection report shall be submitted. All repairs shall be completed | |
08/18/2004 | INSP - FULL | Violation | 2). Fire alarm test and inspection report shall be submitted. All repairs shall be completed. TFC 906.1 | |
08/18/2004 | INSP - FULL | Violation | 3). Fire pump test and inspection report shall be submitted. All repairs shall be completed. TFC 906.1 | |
08/18/2004 | INSP - FULL | Violation | 4). Fire drill required. Date to be determined by September 22, 2004. TFC 404.2 | |
08/18/2004 | INSP - FULL | Violation | 6). Exit signs are out through basement n area. This includes, Maintenance Shop (cover arrow), 5 total. Repair all exit signs. TFC1010.3 | |
08/18/2004 | INSP - FULL | Violation | 7). Cover electrical faceplates, where wiring is exposed. Maintenance shop and record storage are among areas. TFC 605.1 8). Submit emergency generator test log sheet to TFD. TFC 604.3.2 100 North stone cont. |
|
08/18/2004 | INSP - FULL | Violation | 9). Holes shall be repaired, but not limited to the following areas; ceiling by rated hallway door, maintenance shop ceiling, fire control center. TFC 703.1 10). 36-inch aisle shall be created by maintenance shop. TFC 1004.3.1.1 |
|
08/18/2004 | INSP - FULL | Violation | 8). Submit emergency generator test log sheet to TFD. TFC 604.3.2 | |
08/18/2004 | INSP - FULL | Violation | Pima County Print Shop. 11). Exit blocked by paper pallet. Shall be removed. TFC 1011.2 |
|
08/18/2004 | INSP - FULL | Violation | IKE's coffee shop 12) Euscusion shall be refitted on sprinkler head in storage area. TFC 906.1 13). Electrical panel in IKE's storage shall be remained closed at all times. TFC 605.1 |
|
08/18/2004 | INSP - FULL | Violation | First floor empty office 14). Ceiling tile shall be replaced. 703.1 |
|
08/18/2004 | INSP - FULL | Violation | Leopard lounge 15). Exit light shall be repaired 1010.3 |
|
08/18/2004 | INSP - FULL | Violation | Small (intermediate roof) 16). Exit arrows are faded after several of Az heat years. These shall be repainted as per shown. TFC 1010.3. 17). Exit signs shall be illuminated for evening exits. 1010.3 18). Smoke detectors on air ducts shall be addressed on test results 906.1 |
|
08/18/2004 | INSP - FULL | Violation | Suite 500B 19). Extension cord shall be removed through ceiling tiles. TFC605.5 |
|
08/18/2004 | INSP - FULL | Violation | Suite 707 20). Extension cord shall be removed. TFC 605.5 |
|
08/18/2004 | INSP - FULL | Violation | 21). 8th floor sprinkler room Hole in sprinkler room shall be repaired TFC 703.1 |
|
08/18/2004 | INSP - FULL | Violation | Suite 1105 22). Storage shall not be 2 feet with in ceiling TFC 315.2.1 |
|
08/18/2004 | INSP - FULL | Violation | Roof; 23). Standpipes seem to painted shut, shall be loosened TFC 906.1 24). Hole around sprinkler head (computer room) shall be filled. TFC 906.1 Freight elevator room. 25). Hole in walls shall be repaired. 906.1 |
|
08/18/2004 | INSP - FULL | Violation |