Case: T04FR00302

Parcel: 12504079A


Addresses:

1900 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T04FR00302

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/16/2004 INSP - FULL Approved approved
08/13/2004 INSP - FULL Violation 1). Fire drill is required, date for drill to be determined by September 16, 2004. Fire drill requirements as follow as per Tucson Fire Code section 405 and section 406. (Enclosed)
08/13/2004 INSP - FULL Violation 2). Fire alarm panel is showing trouble light, this shall be repaired as per TFC 906.1
08/13/2004 INSP - FULL Violation 3). Exit lights out of service in the following areas and shall be repaired:
Bar area. TFC 1010.3
08/13/2004 INSP - FULL Violation 4). Egress illumination lights are out of service in the following areas and shall be repaired; Bar area, Convention building. TFC 1010.5
08/13/2004 INSP - FULL Violation 5). Certificate of kitchen hood cleaning shall be furnished describing work done, TFC 904.11.6.3
08/13/2004 INSP - FULL Violation 6PoolRoom. Cigarette butts and used matches are found. NO Smoking in pool chemical storage room. TFC 2703.7.1
08/13/2004 INSP - FULL Violation Standpipes seem to paint shut. All shall be open. TFC 906.1
08/13/2004 INSP - FULL Violation 8). All combustible material shall be removed from elevator rooms TFC 315.2.3 This includes all rags not in metal storage as per TFC 304.2
08/13/2004 INSP - FULL Violation 9). Extension cords are running ceiling tiles in Bar area and used as perm. wiring. These cords are subject to mechanical damage. These shall be removed. TFC 605.1