Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T04FR00302
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2004 | INSP - FULL | Approved | approved | |
| 08/13/2004 | INSP - FULL | Violation | 1). Fire drill is required, date for drill to be determined by September 16, 2004. Fire drill requirements as follow as per Tucson Fire Code section 405 and section 406. (Enclosed) | |
| 08/13/2004 | INSP - FULL | Violation | 2). Fire alarm panel is showing trouble light, this shall be repaired as per TFC 906.1 | |
| 08/13/2004 | INSP - FULL | Violation | 3). Exit lights out of service in the following areas and shall be repaired: Bar area. TFC 1010.3 |
|
| 08/13/2004 | INSP - FULL | Violation | 4). Egress illumination lights are out of service in the following areas and shall be repaired; Bar area, Convention building. TFC 1010.5 | |
| 08/13/2004 | INSP - FULL | Violation | 5). Certificate of kitchen hood cleaning shall be furnished describing work done, TFC 904.11.6.3 | |
| 08/13/2004 | INSP - FULL | Violation | 6PoolRoom. Cigarette butts and used matches are found. NO Smoking in pool chemical storage room. TFC 2703.7.1 | |
| 08/13/2004 | INSP - FULL | Violation | Standpipes seem to paint shut. All shall be open. TFC 906.1 | |
| 08/13/2004 | INSP - FULL | Violation | 8). All combustible material shall be removed from elevator rooms TFC 315.2.3 This includes all rags not in metal storage as per TFC 304.2 | |
| 08/13/2004 | INSP - FULL | Violation | 9). Extension cords are running ceiling tiles in Bar area and used as perm. wiring. These cords are subject to mechanical damage. These shall be removed. TFC 605.1 |