Inspection Status: Violation
Inspection History: INSP - FULL
Case Number - T04FR00272
Inspection Description - INSP - FULL
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2004 | INSP - FULL | Violation | all approved 8-19-04 | |
08/05/2004 | INSP - FULL | Violation | 1).Please call Mr. Jim Egan- TFD Plans Review 791-3234 for ventilation needs and requirements. 1). Currently forklift batteries are being charged within 3 feet of combustible material and in an unknown ventilation area. This is violation of: TFC 309.2 Battery chargers. Battery chargers shall be of an approved type. Combustible storage shall be kept a minimum of 3 feet (915 mm) from battery chargers. Battery charging shall not be conducted in areas accessible to the public. 309.3Ventilation. Ventilation shall be provided in an approved manner in battery-charging areas to prevent a dangerous accumulation of flammable gases. |
|
08/05/2004 | INSP - FULL | Violation | 2). Egress illumination shall be maintained as per TFC: 1010.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress. |