Case: T04FR00207

Parcel: 13705289A


Addresses:

5132 S 12TH AV


Inspection Status: Approved

Inspection History: INSP - REINSPECTION

Case Number - T04FR00207

Inspection Description - INSP - REINSPECTION

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2004 INSP - REINSPECTION Approved all approved
08/31/2004 INSP - REINSPECTION Violation 1). Ties shall be 10 feet (if piles are less than 6 feet high) from property lines and all portions of buildings. TFC 2505.4 by TFC 102
Currently tires are adjacent to building rear area north side.
08/31/2004 INSP - REINSPECTION Violation 2). Fire extinguisher shall be mounted and accessible 2A-10BC type required. TFC 906.1
Currently portable fire extinguisher is neither mounted nor accessible.
08/31/2004 INSP - REINSPECTION Violation 3). Smoking is not allowed near tire storage and shall be discarded properly. TFC 2504.3