Case: T04FR00198

Parcel: 12604258D


Addresses:

4301 E 5TH ST

Inspection Status: Compliance

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
07/22/2004 VIOL - BUILDING SVCS & SYSTEMS Compliance TFC 605.6 All repairs made
07/22/2004 VIOL - BUILDING SVCS & SYSTEMS Compliance TFC 605.5 All repairs made.
07/01/2004 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

1. Shall repair junction/outlet box on building located outside southeast corner (by 5th street). Need to make sure box is watertight.
07/01/2004 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5 Extension cords. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
TFC 605.5.3 Maintenance. Extension cords shall be maintained in good condition without splices, deterioration or damage.

1. In hallways you use sound machines, cords going under doors are clear from damage, but need to keep a close watch on cords. During inspection we found chairs, bookshelves and desk on top of cords, this can damage cords and cause electrical shorts and possible fires.
2. In rooms 117, 131, 214 bookshelves are pushing against extension cords crushing the plug into the outlet. This can damage the cord and the outlet and cause an electrical short or fire, need to keep bookshelves and desks from pushing on cord plugs.