Inspection History Details
Inspection Status: Compliance
Inspection History: VIOL - PRECAUTION AGAINST FIRE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2004 | VIOL - PRECAUTION AGAINST FIRE | Compliance | TFC 315.2.3 All repairs made | |
| 07/22/2004 | VIOL - PRECAUTION AGAINST FIRE | Compliance | TFC 315.2.2 All repairs made | |
| 07/22/2004 | VIOL - PRECAUTION AGAINST FIRE | Compliance | TFC 315.2.4 Removed closet from under stairwell, no longer there. | |
| 07/01/2004 | VIOL - PRECAUTION AGAINST FIRE | Violation | TFC 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. 1) Shall remove all combustibles from elevator room 1st floor. |
|
| 07/01/2004 | VIOL - PRECAUTION AGAINST FIRE | Violation | TFC 315.2.2 Means of egress. Combustible materials shall not be stored in exits or exit enclosures. 1.) Shall remove all combustible materials in exit stairwell, you can not have your paper recycle bin in stairwell. |
|
| 07/01/2004 | VIOL - PRECAUTION AGAINST FIRE | Violation | TFC 315.2.4 Attic, under-floor and concealed spaces. Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistive construction. Openings shall be protected by assemblies that are self-closing and are of noncombustible construction or solid wood core not less than 1.75 inches (44.5mm)in thickness. Storage shall not be placed on exposed joists. 1.) Storage room under stairwell (north back door exit) shall meet the requirements listed above. During inspection it was noticed that storage room door, frame and wall was made of wood and not noncombustible. You will need to have approved plans and permits to keep this storage room under exit stairwell or remove all combustible materials. Plans and permits can be obtained from Development services center, 201 N. Stone, Phone 791-5550. |