Case: T04FR00188

Parcel: 11307145A

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T04FR00188

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
10/20/2004 VIOL - FIRE PROTECTION SYSTEMS Approved
08/06/2004 VIOL - FIRE PROTECTION SYSTEMS Denied Re-inspected owner did not have system repaired or up dated. Talked to United fire about hood system, they said when system was put in it met requirements only needing 6 gals of agent. Now today's rquirements they need 9gals of agent and different nozzles. Owner of bus is going to appeal to the chief to keep what he has.
07/13/2004 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 904.1 904.1 General. Automatic fire-extinguishing systems, other than automatic sprinkler systems, shall be designed, installed, inspected, tested and maintained in accordance with the provisions of this section and the applicable referenced standards.

1.) United fire red tag hood system for not having proper coverage. Feild notice given to repair or replace hood extinguisher system. Reinspection on July 27, 2004.