Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/03/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : Install 2 ground rods 6 feet apart with a continuous grounding electrode conn. 1) GROUND RODS MUST BE SET 6'FT ( DISTANT) FROM EACH OTHER. SIX FEET APART. 2) REMOVE TIE BAR BETWEEN GROUND & NEUTRAL BAR ( NEUTRAL MUST BE ISOLATED FROM GROUND AT SUB PANEL) |