Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/28/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 01/24/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* #3 PREVIOUS- 8.3 NM CABLE AMPACITY/IS 40AMPS WE ARE CONNECTED TO A 50AMP BREAKER. #4 PREVIOUS-ENTRANCE ABOVE MANUFACTURES PROVIDED CONCENTRIC KNOCK OUTS ARE CONSIDERED ABOVE CURRENT CARRING PARTS. OK TO CLEAR INCRESE |
| 01/20/2005 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* 1) MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE. 2) RECEPTACLE COVERS TO BE WEATHER PROOF WEATHER OR NOT PLUGED IN 408.6 3) ? CABLE TO TERMINATE AT ?PACITY/ 334.26. 4) A SEALING DEVICE FOR ENTRANCES ABOVE CURRENT CARRING PARTS IS NEEDED. 5) CUSTOMER STATES SHE IS NOT DOING WORK- A LICENSED ELECTRICAL CONTRACTOR IS NEEDED RA?? KIDD'S LICENSE IS NOT IN GOOD STANDING WITH THE REGISTER. |