Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/17/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) J-BOX OVERFILLED SEE CI. ALLOWANCE @J-BOX # 12 IS 2.25 C.I. EACH ( APROX 20 # 12 CONDUCTORS) 2) BOX CONNECTIONS LOOSE AT BELL BOX 3/4" CONDUIT ENTERING 1" KO'S 3) GUTTER 3/4" OPENING IS NOT CLEAN & NO LONGER WEATHER PROOF. 4) CHANGE SQ ? BREAKER TO MURRAY-SIEMENS. 5) OTHER 1/2" BELL BOX IS LOOSE AS WELL ( SECURE 1/2" E.M.T) | |
| 02/11/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO CLEAR |