Permit: T04EL02490

Parcel: 122060810

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/11/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO RECONNECT. 1) BOND JUNCTION BOX ABOVE SERVICE 250.148
12/22/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL PROPER SIZED FUSES AT 60 AMP DISCONNECT SWITCH (S/B 30 AMP MAX)
2) PROTECT N.M. CABLE AT SERVICE EQUIPMENT
3) INSTALL GROUNDING ELECTRODE SYSTEM OR LOCATE EXISTING AND CONNECT TO SERVICE NEUTRAL CONDUCTOR PER NEC
4) REMOVE ZIP CORD WIRING TO WORK SHOP
5) CONTACT TEP SUPERVISOR REGARDING HOW THEY NOW WANT TO HANDLE THIS SERVICE DROP FEED TO WEATHER HEAD
6) REPAIR THE FOLLOWING AND RESCHEDULE INSPECTION