Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO RECONNECT. 1) BOND JUNCTION BOX ABOVE SERVICE 250.148 | |
| 12/22/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL PROPER SIZED FUSES AT 60 AMP DISCONNECT SWITCH (S/B 30 AMP MAX) 2) PROTECT N.M. CABLE AT SERVICE EQUIPMENT 3) INSTALL GROUNDING ELECTRODE SYSTEM OR LOCATE EXISTING AND CONNECT TO SERVICE NEUTRAL CONDUCTOR PER NEC 4) REMOVE ZIP CORD WIRING TO WORK SHOP 5) CONTACT TEP SUPERVISOR REGARDING HOW THEY NOW WANT TO HANDLE THIS SERVICE DROP FEED TO WEATHER HEAD 6) REPAIR THE FOLLOWING AND RESCHEDULE INSPECTION |