Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04EL02480

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/11/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/07/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service entrance is not per code.| 215*
CORRECTIONS:
1) COLD WATER AND GAS PIPING MUST BE GROUNDED TO PANEL.
2) A (DURABLE) METALLIC ADDRESS MUST BE INSTALLED ABOVE OR BELOW METER SOCKET.
3) SIEMENS CIRCUIT BREAKERS CANNOT BE USED IN A CUTLER HAMMER. SEE PANEL TAG.
4) FASTENING HARDWARE TO MOUNT PANEL & RISER HARDWARE IS 1/4 " X ? BOLTS- LAYS - ECT.
5) THE GROUND WIRE MUST BE STRAPPED TO WALL WITH STRAPS MADE FOR THE PURPOSE.
6) MARK ALL YOUR CIRCUITS AT PANEL.
THANKS , CORRECT & RECALL.