Permit: T04EL02478

Parcel: 131030350


Addresses:

5157 E 24TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/06/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*OK TO CLEAR INC
01/05/2005 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*E.M.T CONNECTOR STILL HAS A GAP BETWEEN J-BOX & EDGE OF CONNECTOR. PLEASE CORRECT & RESCHEDULE INSPECTION 740-6970 CALL ME IF YOU HAVE ANY PROBLEMS 954-0161
12/29/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN 1 1/4" EMT CONNECTOR AT J-BOX
2) TIGHTEN BOND BUSHINGS(INSTALL MISSING SET SCREWS)
3) SHEET METAL SCREWS ARE NOT ACCEPTABLE FOR SECURING J-BOX COVERS (USE MACHINE SCREWS-SOULD HAVE COME WITH J-BOX)
4) WHERE IS PANEL DEAD FRONT COVER ?