Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :*/OK TO CLEAR | |
| 12/29/2004 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) RAISE GRADE TO ASSURE 18" MINIMUM DEPTH |
|
| 12/22/2004 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY-UNCOVER GROUNDING ELECTRODE CONDUCTOR ( I NEED TO SEE CONNECTION TO 2ND GROUND ROD, BONDING OF GAS AND WATER PIPING) 2) EXPOSE U.G. CONDUIT OR PROVIDE PREVIOUS INSPECTION APPROVAL RESULTS 3) REPLACE WEATHERED CONDUCTORS AT WEATHER HEAD (USE SUNLIGHT RESISTANT CABLE) |