Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2007 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 02/03/2005 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* OK TO CLEAR INC NOTE: CALL FOR FINAL AFTER TIE IN. ALL EXISISTING OVERHEAD AND UNDERGROUND TO BE ELIMINATED PER APPROVED PLAN. | |
| 01/25/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1) PVC CONDUIT AT POLE NORTHWEST OF SERVICE NOT SUPPORTED. 2) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED TO ENCLOSURE. 3) BOX FOR GFCI OUTLET UNDER SERVICE NOT SUPPORTED. 4) OTHER STRUCTURE FED FROM THIS SERVICE MUST HAVE THEIR OWN GROUNDING ELECTRODE SYSTEM PER ART 250 NEC. 5) WATER & GAS MUST BE BONDED. 6) WIRING UNSAFE AT OTHER UNITS, ( 3) UNITS ? PROVIDE APPROVED PLAN WITH LOAD CALCS FOR DISTRIBUTION OF LOADS, OTHER UNIT WIRING TO BROUGHT UP TO CODE PRIOR TO RELEASE FOR POWER WORK TO BE DONE BY LICENSED CONTR. VERIFY LICENSED CONTR. TO CALL 791-5550 EXT 1136 DAN SANTA CRUZ OR RAY M |