Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04EL02456

Parcel: 110060980

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/24/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR FOR DROP & METER. CORRECTED PER R.H LIST.
01/21/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* NOT READY # 3 OLD INSPECTION SHOUD BE 250.64 ( E) COMPLETE THIS ITEM
01/19/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) BOND BUSHING NEEDED ON CLOSE NIPPLE. 2) FINISH #3 PREVIOUS INSPECTION
01/12/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/1)LB COVER TO BE LOCKABLE ON PRIMARY METER SIDE 2)CHASE NIPPLE NOT APPROVED FITTING. 110.3 & 250.92 3)GROUNDING ELECTRODE CONDUCTOR TO BE INSTALLED PER 250.62 FOR METAL CONDUIT. 4)NO MORE THAN 360 DEGREES IN A CONDUIT RUN 5)PLEASE VERIFY GAS BONDING 6)EFFECTIVELY SEAL UNUSED PORTION OF BACK ENTRANCE 7)CONDUCTOR AMPACITY TO MATCH BREAKER 8)RISER SUPPORTS TO BE RIGIDLY SUPPORTED. 9)PLEASE MAINTANE CLEARENCES FOR SERVICE CONDUCTORS 230.24 10)THIS IS A RENTAL PROPERTY - PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR 11)A PERMANENT METAL ADDRESS LABEL IS NEEDED