Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/24/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* OK TO CLEAR FOR DROP & METER. CORRECTED PER R.H LIST. |
| 01/21/2005 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* NOT READY # 3 OLD INSPECTION SHOUD BE 250.64 ( E) COMPLETE THIS ITEM |
| 01/19/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* 1) BOND BUSHING NEEDED ON CLOSE NIPPLE. 2) FINISH #3 PREVIOUS INSPECTION |
| 01/12/2005 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/1)LB COVER TO BE LOCKABLE ON PRIMARY METER SIDE 2)CHASE NIPPLE NOT APPROVED FITTING. 110.3 & 250.92 3)GROUNDING ELECTRODE CONDUCTOR TO BE INSTALLED PER 250.62 FOR METAL CONDUIT. 4)NO MORE THAN 360 DEGREES IN A CONDUIT RUN 5)PLEASE VERIFY GAS BONDING 6)EFFECTIVELY SEAL UNUSED PORTION OF BACK ENTRANCE 7)CONDUCTOR AMPACITY TO MATCH BREAKER 8)RISER SUPPORTS TO BE RIGIDLY SUPPORTED. 9)PLEASE MAINTANE CLEARENCES FOR SERVICE CONDUCTORS 230.24 10)THIS IS A RENTAL PROPERTY - PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR 11)A PERMANENT METAL ADDRESS LABEL IS NEEDED |