Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/29/2005 | ELECTRIC - SERVICE UPGRADE | Denied | SEE NOTE # 2 IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 09/22/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RISER CONDUIT REQUIRES MINIMUM 1/4" BOLTS TO SUPPORT WALL 2) BOND NEUTRAL BUSS, BOTH SIDES OF 4 METER PACK (MAIN BOND JUMPER) PER NEC 3) REMOVE NEUTRAL BOND JUMPER AT SUB-PANELS, BOND GROUND BAR TO ENCLOSURE 4) LABELS ON SERVICE MUST BE PERMANENT TAGS, SCREWED OR RIVITED TO COVER, NO MARKING PE 5) PLAN CALLS FOR 125 AMP MAINS |