Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/04/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/29/2005 ELECTRIC - SERVICE UPGRADE Denied SEE NOTE # 2
IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
09/22/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RISER CONDUIT REQUIRES MINIMUM 1/4" BOLTS TO SUPPORT WALL
2) BOND NEUTRAL BUSS, BOTH SIDES OF 4 METER PACK (MAIN BOND JUMPER) PER NEC
3) REMOVE NEUTRAL BOND JUMPER AT SUB-PANELS, BOND GROUND BAR TO ENCLOSURE
4) LABELS ON SERVICE MUST BE PERMANENT TAGS, SCREWED OR RIVITED TO COVER, NO MARKING PE
5) PLAN CALLS FOR 125 AMP MAINS