Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* IF NEW CIRCUITS ARE INSTALLED ON INTERIOE, A NEW PERMIT IS NEEDED | |
| 12/17/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BONDING JUMPER TO BE SIZED PER 250.102 AND 250.66 2) BONDING NEEDED PER 250.24 3) WHAT ARE EXTRA BREAKERS FOR ? IS THERE A SET OF ELECTRICAL PLANS AND A PERMIT FOR OTHER WIRING ? YOU HAVE 5-1P 20'S, 2-2P 20'S, 3-3P 30'S, 1-2 P40 AND 1-2P 60 4) NO CIRCUITS ON PERMIT-PLEASE ADD AS NECESSARY |
|
| 12/16/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) THIS SERVICE IS EXISTING 2) COULD NOT UNDERSTAND MESSAGE |