Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)NEED PERMIT FOR 4535 E 17TH 2)BOND BOTH GAS & WATER TO SERVICE 3)PLEASE DRIVE RODS FLUSH OR BELOW GRADE 4)PROVIDE PROPERLY SIZED SUB PANEL FEED S/B 60 AMP MIN. 5)CONNECT GROUNDING ELECTROD DIRECTLY TO NEUTRAL (NOT EQUIP GROUNDING BUS) 6)SECURE RISER W/2ND STRAP EITHER ABOVE ROOF OR INTO MASONRY (SEE TEP SERVICE SPEC & FOR REFERENCE) |