Permit: T04EL02403

Parcel: 135062500

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/16/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/14/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/12/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)WHEN THE ELECTRICAL SERVICE IS UPGRADED IT NOW REQUIRES A NEW GROUND SYSTEM, 2 GROUND RODS 6' APART OR MORE INCLUDING A WATER AND GAS LINE BOND IF ON SITE. 2)SERVICE TO BE PERMANENTLY ADDRESSED NO PEN OR MARKER 3)SEE INSIDE PANEL LABEL ALL CIRCUIT BREAKERS MUST BE OF A TYPE LISTED. 4)NEUTRAL TO BE INDENTIFIED AT WEATHER HEAD 5)2" RISER ABOVE ROOF MUST BE SECURED-GUY BACK WIRES ONLY HOLD RISER BACK-HOWEVER IT IS NOT SECURED ITS LOOSE 6)PANEL TO HAVE CLEARANCE IT'S WIDTH TO GROUND 7)THE FITTINGS FOR 3/4" LB'S ARE THE WRONG TYPE GOING INTO THE PANEL-A CLOSED NIPPLE WITH A LOCK NUT ON INSIDE AND ONE OUTSIDE SCREWED INTO LB 8)GREEN WIRES NOT TO BE USED AS HOT CONDUCTORS